PEERLESS WV Series Installation, Operation & Maintenance Manual page 23

Oil boilers
Table of Contents

Advertisement

Table 7.1: Boiler Ratings
Boiler
Model
Number
GPH¹
✚✪
WBV-03-060-W
0.60
WBV-03-085-W
0.85
WBV-03-105-W
1.05
WBV-04-095-W
0.95
WBV-04-125-W
1.25
WBV-04-150-W
1.50
WBV-05-175-W
1.75
WBV-05-195-W
1.95
®
As an ENERGY STAR
Partner, PB Heat, LLC has determined that these firing rates meet the ENERGY STAR guidelines for energy efficiency.
✝ Top venting only.
Nozzles for these firing rates not provided as standard equipment. Consult factory for price and availability.
✪ This firing rate can only be achieved with a Riello F-3 burner. See Table 5.3.
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.
2 Net water ratings based on an allowance of 1.15.
3 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive
piping systems, etc.
4 Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government tests.
Chimney Size: 8" x 8" x 15 ft.
Input
Boiler
Model
Number
GPH¹
WBV-03-085-S
0.85
1.05
WBV-03-105-S
1.25
WBV-04-125-S
WBV-04-150-S
1.50
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.
2 Net steam ratings based on an allowance of 1.333.
3 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive
piping systems, etc.
4 Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government tests.
Chimney Size: 8" x 8" x 15 ft.
SERIES WBV/WV™ BOILER RATINGS - WATER
Series WBV/WV™- water
Heating
Capacity
Input
MBH
MBH
Water
84
75
119
104
147
126
133
117
175
151
210
180
245
212
273
235
SERIES WBV/WV™ BOILER RATINGS - STEAM
Series WBV/WV™- steam
Heating
Capacity
4
,
MBH
MBH
Steam
119
103
147
124
175
151
210
179
BOILER DIMENSIONS & RATINGS
4
,
AFUE,
Net Ratings
3
Water,
MBH²
Water
65
87.5
90
110
102
87.0
131
157
184
204
Net Ratings
3
Steam
Steam,
Sq. Ft.
MBH²
321
77
388
93
471
113
558
134
%
Water
Content,
gal
11.75
86.2
11.75
85.0
11.75
14.75
85.4
14.75
85.1
14.75
85.5
17.75
85.0
17.75
AFUE,
%
Water
Content,
Steam
gal
84.8
12.00
83.6
12.00
85.3
14.87
84.3
14.87
Minimum
Stack
Draft
Required,
in. W.C.
-0.03
-0.04
-0.05
-0.03
-0.04
-0.05
-0.05
-0.06
Minimum
Stack
Draft
Required,
in. W.C.
-0.04
-0.05
-0.04
-0.05
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbv seriesWbv-03-sptWbv-03-wpc

Table of Contents