Asset Management Function - Vega VEGADIF 85 Operating Instructions Manual

Differential pressure transmitter with metallic measuring diaphragm
Hide thumbs Also See for VEGADIF 85:
Table of Contents

Advertisement

9 Diagnosis, asset management and service
Status messages
62
Modification of a parameter
Switch-on and switch-off times
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
9.3

Asset Management function

The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item " Diagnostics" via the respective adjustment
module.
The status messages are divided into the following categories:
Failure
Function check
Out of specification
Maintenance required
and explained by pictographs:
1
Fig. 45: Pictographs of the status messages
1
Failure - red
2
Out of specification - yellow
3
Function check - orange
4
Maintenance required - blue
Malfunction (Failure):
Due to a malfunction in the instrument, a fault signal is output.
This status message is always active. It cannot be deactivated by the
user.
Function check:
The instrument is being worked on, the measured value is temporarily
invalid (for example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an instrument specification
was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument function is limited. The
measurement is affected, but the measured value is still valid. Plan in
2
3
VEGADIF 85 • Modbus and Levelmaster protocol
4