Status messages
VEGADIF 85 • 4 ... 20 mA
Switch-on and switch-off times
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
8.3

Asset Management function

The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item " Diagnostics" via the respective adjustment
module.
The status messages are divided into the following categories:
Failure
Function check
Out of specification
Maintenance required
and explained by pictographs:
1
Fig. 40: Pictographs of the status messages
1
Failure - red
2
Out of specification - yellow
3
Function check - orange
4
Maintenance required - blue
Failure: Due to a malfunction in the instrument, a fault message is
output.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification: The measured value is unreliable because an
instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required: Due to external influences, the instrument
function is limited. The measurement is affected, but the measured
value is still valid. Plan in maintenance for the instrument because a
failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
8 Diagnosis, asset management and service