Echoflex Installation Guide
Dual Tech Wall-mount Vacancy Sensor

Installation

Note:
Article 725 and local jurisdiction requirements.
The wall-mount sensor is provided with a mounting bracket with pre-
routed wires that can be mounted to a back box. Follow the detailed
instructions for installation.
1. Pull the Belden 8471 (or equivalent) and one 2.5 mm
ground wire to the mounting location (back box or surface mounted
back box) and strip each wire 11 mm (7/16 in).
2. Connect the EchoConnect pigtail wires from the mounting bracket
to the installed wall wires.
a. Connect the data– (black) EchoConnect wire from mounting
bracket to the incoming data– (typically black) wire using a
WAGO wire termination connector (provided).
b. Repeat the above steps for the data+ (white) EchoConnect wire
and for the ESD ground wire (green/yellow), using a new WAGO
connector for each termination type.
3. Orient the mounting plate to the back box with the directional
arrows in the upright position and secure it in place using the
screws provided.
Dual Tech Wall-mount Vacancy Sensor
NEC Class 2 product to be wired in accordance to NEC