ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor Installation Manual page 10

Table of Contents

Advertisement

Echoflex Installation Guide
Dual Tech Wall-mount Vacancy Sensor
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to
10 seconds and allows for simple and quick verification of the sensor's
coverage and range in the installed space.
1. Prepare the site for configuration.
a. Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.
b. You will need direct access to the sensor in order to place it into
Walk Test mode.
2. Press the [Walk Test] button on the bottom of the sensor to enable
the Walk Test feature. A green LED flashes, indicating Walk Test is
enabled and the vacancy timer is shortened to 10 seconds.
3. Move throughout the space, including corners and areas that may
be obscured from line of sight to the sensor. Each time the sensor
detects movement, the lens illuminates red. If acoustic detection is
enabled, any sound detected illuminates the lens green.
4. As needed, adjust the angle of the sensor head to obtain optimal
detection in the space.
5. Walk Test mode automatically exits and the sensor returns to
normal operation after five minutes. You can also manually
terminate by pressing the [Walk Test] button again.
Dual Tech Wall-mount Vacancy Sensor
[Walk Test]
button
Page 10 of 12