Vacancy Timeout; Grace Period; Auto Vacancy Timeout - ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor Installation Manual

Table of Contents

Advertisement

Echoflex Installation Guide
Dual Tech Wall-mount Vacancy Sensor
Custom
When functionality other than Space Off is required, place the sensor in
Custom configuration mode (DIP switch 2 set to On, the default setting).
Customization of the sensor and all actions are configured using the
ElahoAccess App. For more detailed information about custom
configuration options available, see the ElahoAccess App integrated help
system.

Vacancy Timeout

Vacancy timeout is the amount of time the sensor waits to take action
after no movement is detected. By default, vacancy timeout is set to 15
minutes (indicated by DIP switch 3 set to Off and 4 set to On; see
Switches on page 7
begins.
When the sensor detects vacancy, the vacancy timeout period begins. If
the sensor does not detect occupancy again during the vacancy timeout
period, the lights turn off and a 30 second grace period begins.

Grace Period

The sensor features a 30 second grace period after a vacancy timeout
occurs. During this grace period, if the sensor detects occupancy, it will
turn on or restore the previous lighting condition.

Auto Vacancy Timeout

The "Auto" vacancy timeout setting varies the vacancy timeout between
5 and 30 minutes depending on how often it identifies an occupancy
trigger after a vacancy timeout occurs (during the grace period).
Dual Tech Wall-mount Vacancy Sensor
). When the vacancy timeout ends, the grace period