17. Servicing Mode

17.1 Auto OFF/ON Button

1
AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation
can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.
2
TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than
5 seconds. A "beep" sound will heard at the fifth seconds, in order to identify the starting of Test Run
operation (Forced cooling operation). Within 5 minutes after Forced cooling operation start, the Auto OFF/ON
button is pressed for more than 5 seconds. A 2 "beep" sounds will heard at the fifth seconds, in order to
identify the starting of Forced heating operation.
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air
conditioner operation.
Auto OFF/ON button
pressed
Auto Operation
3
REMOTE CONTROL NUMBER SWITCH MODE
The Remote Control Number Switch Mode will be activated if the Auto OFF/ON button is pressed
continuously for more than 11 seconds (3 "beep" sounds will occur at 11th seconds to identify the Remote
Control Number Switch Mode is in standby condition) and press "AC RESET" button and then press any
button at remote control to transmit and store the desired transmission code to the EEPROM.
There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor
unit. The indoor unit will only operate when received signal with same transmission code from remote control.
This could prevent signal interference when there are 2 or more indoor units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
JA
JB
During Remote Control Number Switch Mode, press any button at remote control to transmit and store
the transmission code to the EEPROM.
Main unit always continue Test Run (forced cooling) operation.
5 sec
8 sec
Test Run Operation
Test Run Operation
(Forced Cooling Operation)
(Forced Cooling Operation)
Beep
Beep x 2
Press "AC RESET"
at remote control
11 sec
Remote Control Number
Switch Mode
Beep x 3
Press "AC RESET", then any
key at remote control
Remote Control Printed Circuit Board
Jumper A (J-A)
Jumper B (J-B)
Short
Open
Short
Open
99
16 sec
Remote Control Receiving
Sound OFF/ON
Beep x 4
Press "AC RESET"
at remote control
Remote Control No.
Open
A (Default)
Open
B
Short
C
Short
D