CONTROL UNIT
NOTE!
If the 24 V inputs of many AC drives are connected in parallel, we recommend that
you use a diode in terminal #6 (or #12) to prevent the current to flow in opposite
direction. This can do damage to the control board.
+
#6
Fig. 21: Parallel connection of 24 V inputs with many AC drives
6.2

CONTROL UNIT CABLING

The OPTA1 basic board has 20 control terminals, and the relay board has 6 or 7. You can see
the standard connections of the control unit and the descriptions of signals in Fig. 22.
6.2.1

SELECTION OF THE CONTROL CABLES

The control cables must be a minimum of 0.5 mm
more on the cable types in Table 23 The selection of the correct cable. The terminal wires must
be a maximum of 2.5 mm
AWG) for other terminals.
Table 39: The tightening torques of the control cables
The terminal
Relay and thermistor terminals
Other terminals
6.2.2

CONTROL TERMINALS

Here you see the basic description of the terminals of the I/O board and the relay board. For
more information, see 6.2.2.2 Jumper selections on the OPTA1 basic board. For more
information on control terminals, see All-in-One Application manual.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
-
+
-
+
-
#7
#6
#7
#6
#7
(14 AWG) for the terminals of the relay board and 1.5 mm
2
The terminal screw
M3
M2.6
External
+24V
+
-
#6
#7
(20 AWG) screened multicore cables. See
2
The tightening torque
Nm
0.5
0.2
VACON · 71
(16
2
lb-in.
4.5
1.8
6