Cable And Fuse Sizes For 500-690 V, Fr6 To Fr9 - Vacon NXP/P User Manual

Wall-mounted drives standalone drives
Table of Contents

Advertisement

POWER CABLING
5.3.2

CABLE AND FUSE SIZES FOR 500-690 V, FR6 TO FR9

Table 26: The cable and fuse sizes for Vacon
Frame
Type
0004 6—0007 6
0010 6—0013 6
FR6
0018 6
0022 6
0027 6—0034 6
0041 6
FR7
0052 6
0062 6—0080 6
FR8
0100 6
0125 6—0144 6
0170 6
FR9
0208 6
uses a correction factor 0.7
1)
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
NXS and NXP
®
Fuse
I
[A]
L
(gG/gL) [A]
3–7
10
10–13
16
18
20
22
25
27–34
35
41
50
52
63
62–80
80
100
100
125–144
160
170
200
208
250
Mains,
Terminal cable size
motor and
brake
Mains cable
resistor
terminal
cable Cu
1)
[mm
2
]
[mm
]
2
2.5–50 Cu
3*2.5+2.5
6–50 Al
2.5–50 Cu
3*2.5+2.5
6–50 Al
3*4+4
2.5–50 Cu
6–50 Al
2.5–50 Cu
3*6+6
6–50 Al
2.5–50 Cu
3*10+10
6–50 Al
2.5–50 Cu
3*10+10
6–50 Al
2.5–50 Cu
3*16+16
6–50 Al
3*25+16
25–95 Cu/Al
3*35+16
3*95+50
95–185
Cu/Al2
3*150+70
VACON · 51
Grounding
terminal
[mm
2
]
2.5–35
2.5–35
2.5–35
2.5–35
2.5–35
6–50
6–50
6–95
6–95
5