4.2.24 Shortest acceleration/deceleration mode (Pr. 60 to Pr. 63)

Pr. 60 "shortest acceleration/deceleration mode"
Pr. 61 "reference I for intelligent mode"
Pr. 62 "ref. I for intelligent mode accel"
Pr. 63 "ref. I for intelligent mode decel"
The inverter automatically sets appropriate parameters for operation.
! If you do not set the acceleration and deceleration times and V/F pattern, you can
run the inverter as if appropriate values had been set in the corresponding
parameters. This operation mode is useful to start operation immediately without
making fine parameter settings.
Parameter
Factory
Number
Setting
60
0
61
9999
62
9999
63
9999
" " Acceleration/deceleration reference current (Pr. 61, Pr. 62, Pr. 63)
<Setting1>
Pr. 60
Operation
Mode
Setting
Ordinary
operation
0
mode
Shortest
1, 2, 11,
acceleration/
12
deceleration
mode
Setting Range
0, 1, 2, 11, 12
0 to 500A, 9999
9999: Referenced from rated inverter current.
0 to 200%, 9999
0 to 200%, 9999
Description

Set to accelerate/decelerate the motor in the
shortest time.
The inverter makes acceleration/deceleration in the
shortest time using its full capabilities. During
deceleration, an insufficient brake capability may
cause the regenerative overvoltage alarm (E.OV3).
"1" :
Stall prevention operation level 150%
"2" :
Stall prevention operation level 180%
"11":
Stall prevention operation level 150%
when brake resistor or brake unit is used
"12":
Stall prevention operation level 180%
when brake resistor or brake unit is used
95
PARAMETERS
Related parameters
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Remarks
Automatically
Parameters
Set

Pr. 7, Pr. 8