Mitsubishi FR-E540-0.4K-EC Instruction Manual page 137

Transistorized inverter
Table of Contents

Advertisement

<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter.
After
you
communication cannot be made unit the inverter is reset.
Parameter
Definition
Number
Station
117
number
Communica-
118
tion speed
Stop bit
119*1
length
Parity check
120
presence/
absence
Number of
121
communica-
tion retries
Communica-
122
tion check
time interval
Waiting time
123
setting
have
changed
Setting
Station number specified for communication from the
PU connector.
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800 bps
96
9600 bps
192
19200 bps
0
Communication operation
8 data
1
bits
100
Communication operation
(NET mode communication) Stop bit length 2 bits
101
10
Communication operation
11
7 bits
110
Communication operation
111
(NET mode communication) Stop bit length 2 bits
0
Absent
1
Odd parity present
2
Even parity present
Set the permissible number of retries at occurrence of
a data receive error.
0 to 10
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm
stop.
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can
be coasted to a stop by MRS or RESET input.
9999
During a communication error (H0 to H5), the minor
(65535)
fault signal (LF) is switched on. Allocate the used
terminal with any of Pr. 190 to Pr. 192 (multi-function
outputs).
0
No communication
Set the communication check time [seconds] interval.
If a no-communication state persists for longer than
0.1 to 999.8
the permissible time, the inverter will come to an
alarm stop.
9999
Communication check suspension
Set the waiting time between data transmission to the
0 to 150
inverter and response.
9999
Set with communication data.
the
communication-related
Description
122
PARAMETERS
parameters,
Stop bit length 1 bit
Stop bit length 2 bits
Stop bit length 1 bit
Stop bit length 1 bit
Stop bit length 2 bits
Stop bit length 1 bit