Mitsubishi FR-E540-0.4K-EC Instruction Manual page 134

Transistorized inverter
Table of Contents

Advertisement

<Link start mode>
The operation mode at power on and at restoration from instantaneous power failure
can be selected.
To choose the NET mode communication, set "1" in Pr. 340.
Pr. 340
Operation Mode
Setting
Pr. 79
PU or external
0
operation
1
PU operation
2
External operation
External/PU
3
combined operation
mode
External/PU
0
4
combined operation
(Factory
mode
Setting)
6
Switch-over mode
External operation
7
mode
External/PU
8
combined operation
mode
1
NET mode communication
1) The Pr. 340 value may be changed in any operation mode.
2) When Pr. 79 "operation mode selection" = "0, 2 or 6", "1" in Pr. 340 is made valid.
Mode at Power On or at Restoration
from Instantaneous Power Failure
Inverter goes into the external operation mode.
Inverter goes into the PU operation mode.
Inverter goes into the external operation mode.
Running frequency is set in the PU operation
mode and the start signal is set in the external
operation mode.
Running frequency is set in the external operation
mode and the start signal is set in the PU
operation mode.
Operation mode is switched while running.
MRS signal ON ....Shift to the PU operation mode
enabled (output stopped during
external operation)
MRS signal OFF ..Shift to the PU operation mode
inhibited
X16 signal ON .....Shift to external operation mode
X16 signal OFF....Shift to PU operation mode
Inverter goes into the NET mode communication
mode. (Program need not be used for switching)
119
PARAMETERS