(3) Warnings
Operation Panel Indication
Name
Description
Check point
Corrective action
Note:5 The stall prevention operation current can be set as desired. It is factory-set to
150%.
OL
Stall prevention (over current)
During
If a current of more than 150% (Note 5) of
acceleration
the rated inverter current flows in the
motor, this function stops the increase in
frequency
reduces to prevent the inverter from
resulting in over current shut-off. When the
overload current has reduced below 150%,
this function increases the frequency
again.
During
If a current of more than 150% (Note 5) of
constant-speed
the rated inverter current flows in the
operation
motor, this function lowers the frequency
until the overload current reduces to
prevent overcurrent shut-off. When the
overload current has reduced below 150%,
this function increases the frequency up to
the set value.
During
If a current of more than 150% (Note 5) of
deceleration
the rated inverter current flows in the
motor, this function stops the decrease in
frequency
reduces to prevent the inverter from
resulting in overcurrent shut-off. When the
overload current has reduced below 150%,
this function decreases the frequency
again.
Check the motor for use under overload.
The acceleration/deceleration time may change.
Increase the stall prevention operation level with Pr. 22 "stall
prevention operation level", or disable stall prevention with
Pr. 156 "stall prevention operation selection".
169
PROTECTIVE FUNCTIONS
FR-PU04
OL
until
the
overload
until
the
overload
current
current