Gas Connection; Natural Gas - Fisher & Paykel DCS CPV2-488 Installation Instructions Manual

Professional cooktop
Hide thumbs Also See for DCS CPV2-488:
Table of Contents

Advertisement

Available languages

Available languages

Gas requirements
Verify the type of gas supplied to the location. The cooktop is shipped from the factory set up and adjusted for Natural Gas or LP, depending on the specific model ordered.
Verify that the cooktop is compatible with gas supply at the installation site before proceeding further. Return the cooktop to the dealer if the unit is not set for the gas supplied at the site.

NATURAL GAS

Connection: 1/2" NPT Minimum 5/8" dia. flex line.
LP Gas
Connection: 1/2" NPT Minimum 5/8" dia. flex line.
A regulator is required at the LP source to provide a maximum pressure of 14" W.C. to the cooktop regulator.
Requirements for hook-up to gas supply
A manual shut-off valve (supplied by the installer) must be installed in an accessible location in the gas line external to the appliance for the
purpose of turning on or shutting off gas to the appliance. (In Massachusetts such shut-off valves should be approved by the Board of State
Examiners of Plumbers & Gas Fitters.) The shut-off valve must be located within 6 feet (1.8 meters) of the appliance it serves.
Make sure the gas supply is turned off at the wall valve before connecting the appliance. The gas supply connections should be made by a
qualified technician and in accordance with local codes or ordinances. In the absence of a local code, the installation must conform to the latest
edition of National Fuel Gas Code ANSI Z223.1.
To prepare the unit for connection to the gas supply, thread the supplied 1/2" pipe nipple into the elbow on the end of the manifold.
The elbow is located inside the chassis of the unit, on the end of the manifold, facing down. It is accessible through the square cutout in
the left rear corner of the chassis bottom. Connect the outlet of the regulator to the exposed end of the nipple, connect the flex line from
the gas supply to the inlet side of the regulator.
Warning: this appliance must be installed by a licensed plumber or gas fitter when within the Commonwealth of Massachusetts.
IMPORTANT!
DCS by Fisher & Paykel recommends installing the manual shutoff valve in a location readily accessible by the customer, so that gas to
the appliance can be shut off in an emergency situation. However, the appliance must not be modified in any way to accommodate such
placement.
Pipe sealant must be used on all pipe threads.
The gas supply line must not protrude beyond the back of the appliance.
Make sure the gas supply is turned off at the wall valve before connecting the appliance
Leak-testing of the appliance shall be conducted according to the manufacturer's instructions. See instructions following.
The appliance must be isolated from the building's gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa.). The
appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure
testing of the system at the test pressures in excess of 1/2 psig (3.5kPa.).
When checking the manifold gas pressure, the inlet pressure to the regulator should be at least 7.0" W.C. for natural gas or
12.0" for LP.
The flex line for the gas supply must be metal and be approved for appliance use by a certifying agency (CSA, CGA, or UL).
Never use a hose made of rubber or other synthetic material, as the heat may cause the hose to melt and develop leaks.
The arrow on the regulator indicating direction of gas flow should be pointing towards the unit.
12
!0

GAS CONNECTION

Supply Pressure: 6" to 9" W.C.
Supply Pressure: 11" to 14" W.C.
Threading compound
must be resistant to
LP gas
1/2 x 5" NPT
Close
Nipple
Installer supplied
shut-off valve must be
easily accessible*
*Installation must conform with local
codes or with the National Fuel Gas
Code ANSI Z223.1 or
the CAN/CGA-B149.2 Propane
Installation Code
Flex Line to Cooktop
Manual Shut-o
valve must
!
be easily accessible
Bottom of unit
Coupling
1/2 NPT black
1/2 NPT
Close Nipple
Regulator
LP/NG (included)
Adapter 1/2 NPT to 3/8
flare fitting
Do not put threading
compound on these
threads

Advertisement

Table of Contents
loading

Table of Contents