Baxi LUNA SAT RCZ G1-MB Installation And Operating Manual page 47

Built-in user modules, m-bus models transmission of consumption via cable
Table of Contents

Advertisement

Available languages

Available languages

Status display / Error codes
The symbols in the table below show the meter's operational status. The status messages only appear in the main display
(energy)! The temporary display of the warning triangle can be caused by special operat-ing states and does not always
mean that the device is malfunctioning. However, should the symbol be displayed over a longer period of time, you should
contact the service company..
Symbol
Status
External voltage
Flow existent
Attention!
Symbol flashing: Data transmission
Symbol constantly displayed: optical interface active -
Emergency operation
Error codes show faults detected by zelsius® C5-ISF. If more than one error appears, the sum of the error codes is displa-
yed: Error 1005 = error 1000 and error 5
Code
Error
1
Temperature out of measuring range
2
Temperature out of measuring range
3
Short-circuit return sensor
4
Interruption return sensor
5
Short-circuit supply sensor
6
Interruption supply sensor
7
Battery voltage
8
Hardware error
9
Hardware error
100
Hardware error
800
Wireless interface
1000
Status end of the battery
2000
Status Initial verification expired
Figure 10: meter display
INSTALLATION AND OPERATING MANUAL
Event
-
-
Check system / device for errors
-
Exchange device
Event
Check sensors
Check sensors
Check sensors
Check sensors
Check sensors
Check sensors
Exchange device
Exchange device
Exchange device
Exchange device
Exchange device
Exchange device respectively battery
Exchange device
47
7215037.01 - en

Advertisement

Chapters

Table of Contents
loading

Table of Contents