Installation Instructions: Electrical Connections - Baxi LUNA SAT RCZ G1-MB Installation And Operating Manual

Built-in user modules, m-bus models transmission of consumption via cable
Table of Contents

Advertisement

Available languages

Available languages

The appliance is sold complete with electrical connections and power cable.
This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current
safety regulations.
Connect the appliance to a 230V single-phase earthed power supply using the supplied three-pin cable, observing cor-
rect LIVE (L) - NEUTRAL (N) polarity.
Use a double-pole switch with a contact separation of at least 3mm.
When replacing the power supply cable, fit a harmonised HAR H05 VV-F' 3x1 mm
8mm.
8.1 ACCESS TO THE POWER SUPPLY TERMINAL BLOCK
Disconnect the appliance from the mains power supply using the two-pole switch;
Make sure that the switch indicator light is off.
Loosen the screws on the cover of the electrical box and remove it.
The 2A rapid fuse is incorporated in the power terminal block.
(L)
= LIVE brown
(N)
= NEUTRAL blue
= EARTH yellow-green
Figure 9: Electric fuses
INSTALLATION AND OPERATING MANUAL
INSTALLATION INSTRUCTIONS:
ELECTRICAL CONNECTIONS
8. ELECTRICAL CONNECTIONS
Fuse
Terminal block
cable with a maximum diameter of
2
43
7215037.01 - en