Handling; Mounting And Installation - Siemens KNX RDG400KN Basic Documentation

Room thermostats with communications
Hide thumbs Also See for KNX RDG400KN:
Table of Contents

Advertisement

Mounting
Wiring
· Comply with local regulations to wire, fuse and earth the thermostat
· The power supply line must have an external fuse or circuit breaker with a rated
current of no more than 10 A
· Isolate the cables of inputs X1-M, U1-G0 and D1-GND for AC 230 V if the
conduit box carries AC 230 V mains voltage
· Inputs X1-M or D1-GND: Several switches (e.g. summer/winter switch) may be
connected in parallel. Consider overall maximum contact sensing current for
switch rating
· Isolate the cables of KNX communication input CE+/CE- for AC 230 V if the
conduit box carries AC 230 V mains voltage
· Disconnect the unit from power supply before removing it from its mounting
plate
70 / 86
Siemens
Smart Infrastructure
4.

Handling

4.1

Mounting and installation

Do not mount on a wall in niches or bookshelves, behind curtains, above or near
heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the
floor.
· Mount the room thermostat in a clean, dry indoor place without direct air flow
from a heating/cooling device, and not exposed to drip or splash water
See Mounting Instructions M3192 [3] enclosed with the thermostat.
RDG400KN,RDG405KN Basic documentation
CE1P3192en
2019-04-12