Setpoints And Sequences - Siemens KNX RDG400KN Basic Documentation

Room thermostats with communications
Hide thumbs Also See for KNX RDG400KN:
Table of Contents

Advertisement

Changeover air
Economy, Protection
Application
Y
Single-duct 1)
Single-duct with
Y
electric heater/
radiator/floor
heating
Single-duct with
Y
heating/cooling
coil
SW < 1.24/
device index < C
only: Single-duct
with electric
heater/radiator/
floor heating
W = setpoint in Comfort mode
W
= setpoint heating in Economy or Protection mode
HeatEco/Prot
W
= setpoint cooling in Economy or Protection mode
CoolEco/Prot
Siemens
Smart Infrastructure
3.6.9

Setpoints and sequences

Comfort setpoint (w) is in the currently active heating or cooling sequence.
· If the supply air temperature is available (via KNX), the air
flow may also increase when the room temperature is
below the heating setpoint
· If no supply air temperature is available, the sequence for
air flow control is cooling only
The setpoints for Economy and Protection mode are below the Comfort setpoints
(heating) and above the Comfort setpoints (cooling).
They can be set via P11, P12 (Economy) and P65, P66 (Protection).
w
w
HeatProt
w
w
HeatEco
Comfort mode
Heating
Y
W
T
Y
W
T
Y
W
T
Heating and cooling
Y
W
1) Single-duct: A dead zone can be set also. In this case, the diagram is the same as for single-duct
with electric heater
RDG400KN,RDG405KN Basic documentation
T[°C]
w
CoolProt
CoolEco
Cooling
Y
W
T
Y
W
T
Y
W
T
T
Y = air/water sequence
T = room temperature
The dead zone can be adjusted via P33.
Economy/Protection mode
Heating
Y
T
W
HeatEco/Prot
Y
W
T
HeatEco/Prot
Y
W
T
HeatEco/Prot
Heating and cooling
Y
W
HeatEco/Prot
Cooling
T
W
CoolEco/Prot
T
W
CoolEco/Prot
W
T
CoolEco/Prot
T
45 / 86
CE1P3192en
2019-04-12