Control parameters
Control sequence
Recalibrating the
sensor
Setpoint and range
limitation
Addressing mode
Assigning the KNX
device address
Assigning the KNX
group addresses
KNX serial number
72 / 86
Siemens
Smart Infrastructure
The thermostat's control parameters can be set to ensure optimum performance
of the entire system (see section 3.11).
The parameters can be adjusted using ...
– the local HMI
– Synco ACS
– ETS
· The control sequence may need to be set via P01, depending on the
application. The factory setting is as follows:
Application
Single-duct, single-duct with heating/cooling coil
Single-duct with electric heater, single-duct with
radiator
· Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour
of operation). To do this, change P05
· We recommend to review the setpoints and setpoint ranges (P08...P12) and
change them as needed to achieve maximum comfort and to save energy
The addressing mode helps identify the thermostat in the KNX network during
commissioning.
Press left and right buttons simultaneously for 6 seconds to activate addressing
mode, which is indicated on the display with PrO g .
Addressing mode remains active until thermostat identification is complete.
Assign the device address (P81) via HMI, ACS or ETS.
With device address set to 255, the communication is deactivated (no exchange
of process data).
Use ETS to assign the KNX group addresses of the thermostat's communication
objects.
Each device bears a unique KNX serial number at the rear.
An additional sticker with the same KNX serial number is enclosed in the packa-
ging box. This sticker is intended for installers for documentation purposes.
RDG400KN,RDG405KN Basic documentation
Factory setting P01
1 = cooling only
Not adjustable
CE1P3192en
2019-04-12