Siemens KNX RDG400KN Basic Documentation page 42

Room thermostats with communications
Hide thumbs Also See for KNX RDG400KN:
Table of Contents

Advertisement

Notes
Setting the sequence and the control outputs
42 / 86
Siemens
Smart Infrastructure
Without a valid bus signal for changeover air, the air volume is only increased for
cooling:
2-position radiator/floor heating
Y
100%
Vmax
Vmin
0%
Y
SDH
7.0 mm
ON
YR
W
OFF
dz
22.2 mm
Y
Output signal
TR
Room temperature
W
Effective setpoint Comfort
H
Heating sequence
C
Cooling sequence
YV
Volume flow rate
YR
Radiator/floor heating
· The diagrams only show the PI controller's proportional part
· Switching between heating and cooling depends on the setpoints and the room
temperature (see section 3.6.2)
Refer to sections 0, 3.6.1 and 3.7.
RDG400KN,RDG405KN Basic documentation
Modulating radiator/floor heating
Y
XpC
C
5.2 mm
100%
Vmax
YV
Vmin
0%
TR [°C]
Y
100%
0%
TR [°C]
XpH
Proportional band heating
XpC
Proportional band cooling
Vmin
Minimum volume output
Vmax Maximum volume output
SDH
Switching differential heating
XpC
5.2 mm
YV
TR [°C]
XpH
10.0 mm
YR
W
dz
TR [°C]
14.3 mm
CE1P3192en
2019-04-12
C