3.13 Control parameters

A number of control parameters can be readjusted to optimize the control
performance. This can be done on the thermostat via HMI or via commissioning/
operating tool. These parameters can also be set during operation without
opening the unit.
In the event of a power failure, all control parameter settings are retained.
The control parameters are assigned to 2 levels:
· Service level, and
· Expert level including communications, diagnostics and test
The Service level contains a small set of parameters to set up the thermostat for
the HVAC system and to adjust the user interface. These parameters can be
adjusted any time.
Change parameters at the Expert level carefully, as they impact the thermostat's
control performance and functionality.

3.13.1 Parameter setting via local HMI

1.
Hold down both the left and right buttons simultaneously for 4 seconds.
Release them, and hold the right button again within 2 seconds until P01
displays.
Continue with step 2.
1. Hold down both the left and right buttons simultaneously for 4 seconds.
Release them, and hold the left button again within 2 seconds until the
temperature disappears.
Turn the rotary knob counterclockwise minimum ½ rotation. Pxx displays.
Continue with step 2.
2.
Select the required parameter by turning the rotary knob.
3.
Press button
(OK); the current value of the selected parameter starts
blinking and can be changed by turning the rotary knob.
4.
Press button
(OK) to confirm the adjusted value or press button
(Esc) to cancel the change.
5.
If you wish to adjust additional parameters, repeat steps 2...4.
6.
Press button
(Esc) to leave the parameter setting mode.
The factory setting for the control parameters can be reloaded via P71 by
changing the value to "On". Confirm by pressing the right button.
Then, 8888 displays during reloading.
RDG400KN,RDG405KN Basic documentation
65 / 86