Control Parameters - Siemens RDB160BN Basic Documentation

Room thermostat with bacnet ms/tp communication
Table of Contents

Advertisement

8
Communication

Control parameters

8.3 Control parameters
32 | 52
Object
Object ID
name
ROpMod
Multistate
value, 5
Multistate
BtnCnf
value, 6
Valve 1
Multistate
setting
value, 7
Valve 2
Multistate
setting
value, 8
A number of control parameters can be readjusted to optimize control
performance. This can be done on the thermostat via HMI or via commissioning
/ operating tool. These parameters can also be set during operation without
opening the unit.
All control parameter settings are retained in the event of a power failure.
Description
Values
Room operating
1 = Off
mode
2 =
Economy/Standb
y
3 = Not used
4 = Not used
5 = Comfort
6 = No remote
control
1 = No active
Buttons active
buttons
2 = Only On/Off
button active
3 = Only
Up/Down
buttons active
4 = On/Off and
Up/Down
buttons active
5 = Only fan
button active
6 = On/Off and
fan button active
7 = Up/Down
and fan button
active
8 = All buttons
active
Set valve 1 type
1 = DC valve
2 = PWM
3 = On/Off
4 = 3-position
valve
Set valve 2 type
1 = DC valve
2 = PWM
3 = On/Off
4 = 3-position
valve
Writeable
Yes
Yes
Yes
Yes
A6V11917618_en--_b