Routine Maintenance - Sungrow SG110CX User Manual

Pv grid-connected inverter
Hide thumbs Also See for SG110CX:
Table of Contents

Advertisement

User Manual
NOTICE
Restart the inverter only after removing the fault that impairs safety performance.
As the inverter contains no component parts that can be maintained, never open the
enclosure, or replace any internal components.
To avoid the risk of electric shock, do not perform any other maintenance operations
beyond this manual. If necessary, contact your distributor first. If the problem per­
sists, contact SUNGROW. Otherwise, the losses caused is not covered by the war­
ranty.
NOTICE
Touching the PCB or other static sensitive components may cause damage to the
device.
• Do not touch the circuit board unnecessarily.
• Observe the regulations to protect against electrostatic and wear an anti-static
wrist strap.

9.2.2 Routine Maintenance

Item
Device clean
Fans
Cable entry
Method
Check whether the air outlet and heat
sink are blocked by dust and other ob­
jects.
Check if the air inlet and outlet are nor­
mal. Clean the air inlet and outlet, if
necessary.
Check whether there is a fan alarm on
the App.
Check whether there is any abnormal
noise when the fan is rotating.
Clean or replace the fans if necessary
(see the following section).
Check whether the cable entry is insuf­
ficiently sealed or the gap is excessive­
ly large, and reseal the entry when nec­
essary.
9 Troubleshooting and Maintenance
Period
Six months to a year
(depend on the dust con­
tents in air)
Once a year
Once a year
109