Control Circuit Protection - Vogt TUBE-ICE 03TB Service Manual

Table of Contents

Advertisement

9-10
SERVICE OPERATIONS
The CoreSense module has power applied at all times to allow for more detailed fault
notification. An LED will flash when a fault occurs. The number of flashes will identify the
fault condition.
# of Flashes
1
2
3
4
5
Description
Crankcase Heater
Oil Pressure safety switch
CoreSense Protection
Oil safety – sensor only
Control Circuit Protection. The electrical control circuit of the machine is protected by a 2 pole 3
amp circuit breaker. If breaker trips, the machine will immediately stop. Before resetting the
breaker, open the disconnect switch to machine and set the "Ice/Off/Clean" switch to the "Off"
position. If the machine was off for an extended time the crankcase heater must be energized for a
minimum of two hours before restarting the machine. When ready to restart the machine, depress
the "Start" button. The machine will automatically return to a freeze cycle upon completion of the
harvest cycle.
4/11/14
Condition
Oil Pressure
Motor Protection Trip
Discharge Temperature (optional add-on)
Current Sensor Fault
Communication Error
3
22
22
6
CoreSense Protection
100 W (insert type)
Sentronic3
Module and Sensor
Module and Sensor
For Sentronic, Sentronic 3
or CoreSense
FIGURE 9-9B
12A7509E12
12A2117A05
12A2117A07
12A2117A0501
03TA Service Manual
Vogt #
Copeland #
518-0028-01
585-1076-02
943-0109-00
998-0162-00