Power Monitor Parameters, Table 10-1 - Vogt TUBE-ICE 03TB Service Manual

Table of Contents

Advertisement

10-2
OPTIONS AND ACCESSORIES
Parameter limits
Parameter
Line Side Voltage
(Nominal Voltage)
Over Voltage
(tolerance)
Under Voltage
(tolerance)
Phase Unbalance
Lockout Time
(Delay on Break)
Delay Time
(Delay on Make)
Response Time
(Delay on Fault)
Control Mode
Contactor Test
Parameters adjustment (in order of display)
Active display of Line Voltage (this is the default normal display)
Active display of Load Side Voltage (if connected)
Voltage Set Point
(VAC Flashes) The value may be adjusted by pressing the up and down arrows. This may be set to the normal
operating voltage of the device being protected in one volt increments.
Under/over Voltage Tolerance in %
(UNDERVOLTAGE/OVERVOLTAGE flashes)
The value may be adjusted by pressing the up and down arrows.
Imbalance Voltage Tolerance in %
(% IMBALANCE flashes) The value may be adjusted by pressing the up and down arrows.
Lockout Time in seconds
(SECONDS flashes) The value may be adjusted by pressing the up and down arrows. (This is the delay on break timer
value)
Delay time in seconds and tenths of seconds
(RESP. SECONDS flashes) The value may be adjusted by pressing the up and down arrows. This is the time that a
fault is allowed before shutdown occurs.
Control mode
(ON OFF AUTO flashes) The value may be adjusted to OFF (load will not turn on), ON (load will turn on whenever
there are not faults and timers are finished) and AUTO (Load will turn on when there is a control input).
Contactor fault monitor mode
(CONTACTOR FAULT flashes) This option allows you to monitor the contactor and lock it out if the line voltage and
load side varies by more than 5 volts. Pressing the up and down arrows selects off (default) or on. The load side of the
contactor must be connected to the load terminals of the DTP-3 to use this option.
Display of fault memories
(MEM flashes) Pressing up or down displays the last fault conditions that took the unit off line. The first 25 faults are
recorded. The top number displayed represents the fault memory. The middle number represents the total number of
faults that have occurred since the fault memory was cleared.
To clear the memory, press and hold the up and down keys until the display is cleared.
Minimum
Maximum
90
650
6
18
6
18
2
25
0.1
25
0
30
0.1
20
Off / Auto / On
OFF
5
TABLE 10-1
Power Monitor Parameters
Default
Recommended Settings
208
Supply voltage
12
10
12
10
6
5
0.5
120
0
0
2
2
Auto
On
OFF
OFF
03TA Service Manual
Unit
Volts
%
%
%
Seconds
Seconds
Seconds
N/A
Volt Diff