03TA Service Manual
15. After installation, the field installed lines are to be evacuated to a vacuum of 500 microns or less
and held for at least one hour. After the vacuum pump is removed, vacuum should hold at 500
microns or less for at least 5 minutes.
16. The machine is shipped with a full operating charge of refrigerant sufficient to fill the condenser
and connecting lines. If the condenser piping is longer than 50 feet (one way), additional R-22
or R-404a may need to be added to retain enough refrigerant in the receiver for thawing purposes
(see table. Refer to the operating level mark on the receiver and charge accordingly. Each 1" of
liquid level in the receiver equals approximately 5.5 pounds of R-22 or R-404a.
Liquid Line Size
1/2"
5/8"
7/8"
1-1/8"
17. All piping must be done in accordance with applicable local and national codes. Such codes may
include "The Safety Code For Mechanical Refrigeration" (ANSI B9.1) and "The Code For
Refrigerant Piping" (ANSI B31.5).
18. The following installation guidelines are strongly suggested. While they do not affect the
machine warranty, they may be required for safe operation and to comply with all applicable
electrical and mechanical codes:
a. Local electrical code must be checked for wiring method.
b. The installer must provide a disconnect switch(s) adjacent to the condenser.
c. Electrical connections between the condenser and the Tube-Ice
minimum 12 ga. wire.
d. All electrical fittings and components exposed to the weather must be suitable for
outdoor installation.
The design total heat rejection for each Tube-Ice
and condenser physical and electrical data are shown on the next page. Specified energy efficiency
ratings of the ice machines are based on use of the recommended condenser and approved piping
practices.
Recommended condensers provide the indicated total heat rejection at 90°F ambient, 100°F
condensing.
Vogt Ice, LLC is not responsible for head pressure problems if other than the
recommended condensers are used. For continuous operation at ambient temperature above 105°F,
consult the factory about using a larger condenser.
75 ft.
none
none
none
none
TABLE 3-3
Pounds of R-22 / 404A to Add vs. Liquid Line Length
INSTALLING YOUR TUBE-ICE
100 ft.
125 ft.
None
None
2
4
4
8
6
12
®
machine require
®
machine, the recommended air-cooled condenser,
3-11
®
MACHINE
150 ft.
2
6
12
18