1MRK 505 339-UEN B
Section 7
7.1

Communication via the rear ports

7.1.1

LON communication

LON communication is normally used in substation automation systems. Optical fiber is used
within the substation as the physical communication link.
The test can only be carried out when the whole communication system is installed. Thus, the
test is a system test and is not dealt with here.
IED
IEC05000663 V2 EN-US
Figure 9:
An optical network can be used within the substation automation system. This enables
communication with the IEDs through the LON bus from the operator's workplace, from the
control center and also from other IEDs via bay-to-bay horizontal communication.
The fiber optic LON bus is implemented using either glass core or plastic core fiber optic
cables.
Commissioning manual
Establishing connection and
verifying the LON communication
Station HSI
MicroSCADA
Star coupler
RER 111
IED
Example of LON communication structure for a substation automation
system

Establishing connection and verifying the LON communication

Control Center
Gateway
IED
IEC05000663-1-en.vsd
Section 7
M12196-2 v1
M12196-4 v4
M14804-3 v3