ABB RELION 670 Series Commissioning Manual page 106

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
4.
Check the measured time by comparing it to the set trip time
5.
Increase the voltage until START signal resets. Measure the time from reset of START
signal to reset of TRIP signal.
6.
Check the measured time by comparing it to the set trip reset time
10.4.4.4
Final adjustment of compensation for VT ratio differences
Procedure
1.
With the protection in test mode, view the differential voltage service values in each
phase on the local HMI under Main menu/Test/Function status/Voltage protection/
VoltageDiff(PTOV,60)/VDCPTOV:x.
2.
Record the differential voltages.
3.
Calculate the compensation factor
For information about calculation of the compensation factor, see the application
manual.
4.
Set the compensation factors on the local HMI under Main menu/Settings/Settings
group N/Voltage protection/VoltageDiff(PTOV,60)/VDCPTOV:x
5.
Check that the differential voltages are close to zero.
10.4.4.5
Completing the test
Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
10.4.5
Loss of voltage check LOVPTUV
Prepare the IED for verification of settings as outlined in the section
this chapter.
10.4.5.1
Measuring the operate limit of set values
1.
Check that the input logical signals BLOCK, CBOPEN and VTSU are logical zero.
2.
Supply a three-phase rated voltage in all three phases and note on the local HMI that the
TRIP logical signal is equal to the logical 0.
3.
Switch off the voltage in all three phases.
After set
local HMI.
4.
Inject the measured voltages at rated values for at least set
5.
Activate the CBOPEN binary input.
6.
Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
7.
Inject the measured voltages at rated values for at least set
100
The IED voltage inputs should be connected to the VTs according to valid
connection diagram.
tTrip time a TRIP signal appears on the corresponding binary output or on the
Note that TRIP at this time is a pulse signal, duration should be according
tPulse .
to set
RFLx for each phase.
1MRK 505 339-UEN B
tTrip .
tReset .
SEMOD175258-183 v2
SEMOD175258-208 v2
TestMode setting to Off .
SEMOD175023-3 v5
"Preparing for test"
SEMOD175023-7 v7
tRestore time.
tRestore time.
Commissioning manual
in

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents