Combustible Surface Required Clearances - HearthStone 8680 Owner's Manual

Table of Contents

Advertisement

C
S
OMBUSTIBLE
URFACE
Note: Dimensions shown in the following figures are from the body of the stove unless otherwise indicated.
It is very important to follow minimum clearances for chimney connectors to combustibles such as walls and
ceilings when installing the stove near combustible surfaces.
Clearances
Single wall Connector –
Single Wall Connector –
Double Wall Connector –
Double Wall Connector –
Alcove W/Single Wall Conn –
Alcove W/Single Wall Conn –
Alcove W/Dbl Wall Conn –
Alcove W/Dbl Wall Conn –
Alcove Clearances (inches)
Minimum alcove width
Min. Alcove ceiling from floor with single wall connector 61.5" – 156.2cm
Min. Alcove ceiling from floor with double wall connector 61.5" – 156.2cm
FOR BLOWER KIT, USE KIT #96-57800
Hearthstone Quality Home Heating Products, Inc ®
R
C
EQUIRED
Figure 4 – Clearance to Combustibles
Parallel
13"-33cm 8"-20cm 13"-33cm
Inc. Rear Heat Shield
13"-33cm 8"-20cm 13"-33cm
With Blower Kit Shield
13"-33cm 8"-20cm 13"-33cm
Inc. Rear Heat Shield
13"-33cm 5"-13cm 10"-26cm
With Blower Kit Shield
13"-33cm 8"-20cm 13"-33cm
Inc. Rear Heat Shield
13"-33cm 8"-20cm 13"-33cm
With Blower Kit Shield
13"-33cm 8"-20cm 13"-33cm
Inc. Rear Heat Shield
13"-33cm 8"-20cm 13"-33cm
With Blower Kit Shield
LEARANCES
A
B
Unprotected Surfaces Protected Surfaces (NFPA-211)
54.5" – 138.4cm
10
Corner
C
D
E
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
28"-71cm
7"-18cm 20.5"-52cm
See NFPA-211
See NFPA-211
See NFPA-211
Green Mountain 80 (Model 8680)
Corner
F

Advertisement

Table of Contents
loading

This manual is also suitable for:

Green mountain 80