Test Boiler; Commercial Boilers - Riello RS 45 BLU Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

3.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the
manufacturer.
3.8.1

Commercial boilers

The burner is suitable for operating on both flame inversion boil-
ers as well as on boilers with a combustion chamber with run-off
from the bottom (three flue passes) on which the best results for
low NO
emissions are obtained.
x
The maximum thickness of the boiler front door must not exceed
200 mm (see Fig. 4).
The coupling is ensured when the boiler is EC type-approved; for
boilers or ovens with combustion chambers of very different di-
mensions compared to those shown in the diagram of (Fig. 3)
preliminary checks are recommended.
200 mm MAX
D1079
20191684
Technical description of the burner
Fig. 4
10
GB
The firing rates were set in relation to special test boilers,
according to EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test
combustion chamber.
Example:
Output 400 kW: diameter 50 cm - length 1.5 m.
D497
Fig. 3