Installation Requirements
Gas Requirements
Provide Adequate Gas Supply
This oven's installation must conform to local codes or, in their absence, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54.
This range's cooktop is designed to operate at a manifold pressure of 5 in. (13 cm) of water column
for natural gas/natural gas at high altitude (NG-H) or 10 in. (25.4 cm) of water column for LP
(propane)/LP at high altitude (LP-H).
Verify that the oven is right for the provided gas service.
When verifying regulator function, inlet pressure must be at least 1 in. (2.5 cm) greater than the
operating (manifold) pressure as given.
Gas Type
Natural Gas
LP (propane) Gas
*The gas supply pressure for testing the regulator setting shall be at least 1" water column (249 Pa) above the
specified manifold pressure; **Maximum gas supply pressure for all models: 1/2 psi.
NOTE
• The pressure regulator at the inlet of the cooktop manifold must stay in the supply line whether
or not natural or LP gas is used.
• Use only the range's regulator, which must be installed in the gas line that runs from the
cooktop gas inlet to the gas shut-off valve.
• An external manual shut-off valve must be installed between the gas inlet and range for turning
on/off gas to the appliance.
• Ensure the connectors are installed by a qualified installer.
• To avoid leaks and personal injury, never install used connectors on a new product. Use only
new, flexible connectors.
Special Gas Requirements (gas models sold in Massachusetts)
WARNING
• Gas leaks may occur in your system, creating a hazardous condition. Such leaks may not be
detected by smell alone; thus, gas suppliers recommend installing a UL-approved gas detector
per manufacturer specifications.
• The range must be installed by a plumber or gas fitter certified by the State of Massachusetts.
• A T-handle manual gas valve MUST be installed in the gas-supply line to your range.
• If using a flexible gas connector, multiple lines must not be connected in series.
18 English
GAS SUPPLY PRESSURE REQUIREMENTS*
Minimum Manifold Pressure
5" Water Column
10" Water Column
Minimum Gas Supply Pressure**
6" Water Column
11" Water Column