4.2.18 Automatic restart after instantaneous power failure
(Pr. 57, Pr. 58)
Pr. 57 "restart coasting time"
Pr. 58 "restart cushion time"
! You can restart the inverter without stopping the motor (with the motor coasting)
when power is restored after an instantaneous power failure.
Parameter
Factory
Number
Setting
57
58
<Setting>
Refer to the following table and set the parameters:
Parameter
Setting
Number
0.1K to 1.5K
0
2.2K to 7.5K
57
0.1 to 5 s
58
0 to 60 s
Power supply
(R(L1), S(L2), T(L3))
STF(STR)
Motor speed
(r/min)
Inverter output
frequency
(Hz)
Inverter output
voltage
(V)
Setting Range
9999
0 to 5 s, 9999
1.0 s
0 to 60 s
0.5 s coasting time
1.0 s coasting time
Waiting time for inverter-triggered restart after power is restored
from an instantaneous power failure. (Set this time between 0.1s
and 5s according to the inertia moment (J) and torque of the
load.)
9999
No restart
Normally the inverter may be run with the factory settings. These
values are adjustable to the load (inertia moment, torque).
Instantaneous power
failure (power failure) time
Coasting time
Pr. 57 setting
Get other manuals https://www.bkmanuals.com
Remarks
9999: No restart
Description
Generally use this setting.
Restart
voltage
rise time
Pr. 58 setting
81
PARAMETERS