DOK-INDRV*-HMV01******-IT01-EN-P
Rexroth IndraDrive Supply Units HMV01
View
Terminal block
Screw thread
Tightening torque
Connection cables
Stranded wire with ring cable lug
Occurring current load and minimum required
connection cross section
Occurring voltage load
5.2.4

X13, Supply Fan Unit HAB01

Description
Identification
Unit
Nm
mm
2
AWG
A
V
Fig.5-7:
X3, Mains Connection
Via this connection, the HAB01 fan unit of HMV01.1R‑W0120 and
HMS01.1N-W0350 devices is supplied with voltage (24V, 0V). The connec‐
tion is situated at the bottom of the device.
NOTICE
Always operate HMV01.1R-W0120 and HMS01.1N-W0350 with the HAB01
fan unit.
Do not operate any other loads at connection X13.
Bosch Rexroth AG
Function 3‑phase operation
Min.
M10
16
1×16; 1×25; 1×35; 1×50; 1×70; 1×120
2×16 (with different angles)
2×25; 2×35; 2×50; 2×70; 2×120
1×6; 1×4; 1×2; 1×1; 1×1/0; 1×2/0; 1×4/0
2×6 (with different angles)
2×4; 2×2; 2×1; 2×1/0; 2×2/0; 2×4/0
See technical data of device used (I
See technical data of device used (U
U
LN_nenn
Risk of damage by overheating!
37/81
Instructions for Use
Max.
20
and A
)
LN
LN
or
LN
)

Advertisement