Rexroth IndraDrive Supply Units HMV01
Notes on Installation
5.2.10
X40, Acknowledge Messages of External Mains Contactor
Function, Pin Assignment
Connection Diagram
Use
●
mains contactors with overvoltage limiter at the contactor coil
●
preferably contactors with AC excitation (if necessary, use conversion
contactor)
When selecting mains contactor K1 and, if necessary, contactor relay K11,
observe the maximum allowed delay time:
The mains voltage must have been applied to the input terminals X3 at the
latest 100 ms after the control signal was output. Otherwise, "F2835 Mains
contactor wiring error" is signaled.
The connection point X40 is available at supply units HMV01.1R-
W0120 with hardware index ≥ A11 (see type plate). These supply
units do not have connection point X33.
View
Fig.5-26:
View
Pin assignment
Supply units with external mains contactor
HMV01.1R-W0120
The contacts are included in the control circuits for mains connection (see Project
Planning Manual of drive system).
Fig.5-27:
Function, Pin Assignment
Supply units without integrated mains contactor
Bosch Rexroth AG
Connec‐
Signal
Function
tion
name
Receives message signals on
the status of the external mains
contactor.
4
-
A) Connect N/O contact of exter‐
nal mains contactor
3
-
2
-
B) Connect N/C contact of exter‐
nal mains contactor
1
-