Parameter Group 6, Service And Diagnostics - Danfoss VLT 3500 HVAC Manual

Table of Contents

Advertisement

Service and diagnostics, group 6..
In group 6.., different operating data can be recorded
that may be used in connection with service and
diagnostics. Also, this group contains information
about the identity of the unit and the software
version used.
600 Operation data (OPERATION DATA)
Value:
0
Total number of operating hours
(TOT.HRS xxxx) *)
1
Running hours (RUN.HRS xxxx)*)
2
kWh (ENERGY xxxx)
3
No. of cut-ins (POW-UPS xxxx)
4
No. of overheatings (OV.TEMP xxxx)
5
No. of overvoltages (OV.VOLT xxxx)
Function:
[Index 000.00-005.00]
Display of the most important operation data.
Description of choice:
Display range:
Total number of operating hours/Running hours/kWh
is 0.0 - 99999 (below 10000, with 1 decimal).
Number of cut-ins/Number of overheatings/Number
of overvoltages is 0 - 99999.
Serial communication:
Total number of operating hours/Running hours/kWh
is registered in the form of floating decimal point
values.
No. of cut-ins/Number Overheatings/Number
Overvoltages, registered as whole numbers.
Total number of operating hours/Running hours/kWh is
automatically reset after manual initialisation.
NB!:
NB!:
NB!:
NB!:
NB!:
The data stated are saved every 8 hours. kWh
can be reset via parameter 011.
Running hours can be reset via parameter 012.
Number of cut-ins/Number of overheatings/Number
of overvoltages are saved as they occur.
= factory setting. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
MG.35.B1.02 – VLT is a registered Danfoss trademark
VLT
®
3500 HVAC
601 Data log (DATALOG)
Digital inputs
(DIG.IN)
Control word
(CONTRL) [1]
Status word
(STATUS) [2]
Reference %
(REF. %)
Frequency out
(F-OUT)
Phase current
(IPHASE) [5]
DC voltage
(UDC)
Function:
[Index 000.00 - 019.06]
Logging of data for the last few seconds of operation,
before stop or trip.
Description of choice:
Digital inputs are stated in hex code
(0-FF).
Control words are stated as a hex code
(0-FFFF) for bus operation RS 485.
Status words are stated as a hex code
(0-FFFF) for bus operation RS 485.
Reference is the control signal in percent (0-100%).
Frequency out is the output frequency of the unit in
Hz (0.0 - 999.9).
Phase current is an output current in A (0.0 - 999.9).
Direct voltage indicates the voltage of the
intermediate circuit in [V DC] (0-999).
20 log values are stated (0-19).
The lowest number (0) contains the most recent/last
data value saved; the highest log number (19)
contains the oldest data value.
Data values log every 160 msec. as long as the start
signal is active.
The data log contains the 20 last log values (approx.
3.2 sec.) before a stop signal is given (start not
active), or a trip occurs.
It is possible to scroll through the log values. The data
log is reset during start up (when the mains supply is
restored).
0 1 2 3 4 - -19
[0]
[3]
[4]
[6]
71