Installation & User Manual
CAUTION: A battery can present a risk of electrical shock and high short-circuit current.
The following precautions should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Determine if battery is inadvertently grounded. If inadvertently grounded, remove source
from ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during
installation and maintenance.
CAUTION: Risk of electric shock. Do not remove cover. No user serviceable parts inside.
Refer servicing to qualified service personnel.
WARNING: To reduce the risk of fire, replace only with the same type and rating of fuse.
CAUTION: A disconnect switch must be provided by others for the AC output circuit. To
reduce the risk of fire, connect only to a circuit provided with branch circuit over-current
protection for 30 amperes for 4.5 to 6kVA rating or 50 amperes for 8 to 10kVA rating in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION: To reduce the risk of fire connect the UPS only to a circuit provided with branch
circuit over-current protection of 30 amperes for 4.5kVA rating, 45 amperes for 6kVA rating or
75 amperes for 8 to10kVA rating in accordance with the National Electric Code, ANSI/NFPA 70.
This UPS should be installed according to the instructions in this manual. Failure to do so could
result in unsafe operation and could invalidate your warranty.
This device is not intended for life support applications.
The maximum UPS output load (in watts) must never exceed that shown on the UPS rating
label.
NEVER CONNECT equipment that could overload the UPS or demand half-wave rectification
from the UPS, for example: electric drill motors, vacuum cleaners, or hair dryers. Do not attempt
to apply source voltage into the UPS output.
Storing magnetic media on top of the UPS may result in data loss or corruption.
This UPS is equipped with an EMI filter. To prevent potential leakage current hazards, ensure
that the AC mains supply is securely grounded.
To ensure safety for a hard-wired UPS, the system must be installed by a licensed electrician.
This UPS includes a Maintenance Bypass Switch. Please follow the procedures when installing
or operating the Maintenance Bypass Switch.