Falcon FN2-4.5K-2TXI Installation & User Manual page 21

Table of Contents

Advertisement

Installation & User Manual
Terminal 1
Terminal 1
Terminal 2
G2
Ground
Jumper to
Jumper to N11
N22 / N11
Notes:
The maximum current for each terminal is 36 Amps RMS for 4.5 to 6kVA, 65 Amps RMS
for 8 to 10kVA.
Single Input Configuration UPS, AC source can be supplied to the UPS from the L12 to
N1 terminals.
For 120Vac output only application, output terminal N22 must use AWG #8 wire
connected to ground. (Neutral Bonding)
AC Input / Output Current and Wire Recommendation
Model
4.5kVA
6kVA
8kVA
10kVA
120V
Output Configuration Table (120V)
Terminal 3
N22
N11
0V
0V
Jumper to N22
Neutral
Maximum
Current
Input: Use #10 AWG, 75°C copper wire, TRQ: 12 IN LB
30A (Input)
30A (Output)
Output: Use #10 AWG, 75°C copper wire, TRQ: 12 IN LB
Input: Use #8 AWG, 90°C copper wire, TRQ: 12 IN LB
36A (Input)
36A (Output)
Output: Use #8 AWG, 75°C copper wire, TRQ: 12 IN LB
Input: Use #6 AWG, 90°C copper wire, TRQ: 18 IN LB
52A (Input)
40A
Output: Use #8 AWG, 90°C copper wire, TRQ: 10 IN LB
(Output)
Input: Use #4 AWG, 90°C copper wire, TRQ: 18 IN LB
62A (Input)
50A (Output)
Output: Use #6 AWG, 90°C copper wire, TRQ: 10 IN LB
Terminal 4
Terminal 5
L22
120V
Jumper to L11
Jumper to L22
Line
Conductor Selection
FN2 Series OM480051 Rev.: E
Falcon Electric, Inc.
Terminal 6
L11
L12
120V
88V
Not
Used
21