Digital Output Wiring - Zmotion EIO1616 Manual

Ethercat bus expansion module
Table of Contents

Advertisement

Voltage level
Max output current
Max leakage current when off
Respond time to conduct
Respond time to close
Overcurrent protection
Isolation method
Note:
The times in the form are typical based on the resistive load, and may change
when the load circuit changes.
Due to the leak-type output, the shutdown of the output will be obviously
affected by the external load circuit, and the output frequency should not be set
too high in the application. And it is recommended to set below 8KHz.

3.3.2. Digital Output Wiring

→ Wiring Note:
The wiring principle of digital outputs OUT (0-15) is shown in the figure above. The
external signal receiving end can be an optocoupler or a relay or solenoid valve, all
can be connected as long as the input current does not exceed 300mA.
EIO1616 Bus Expansion Module User Manual V1.5
DC24V
+300mA
25μA
12μs
80μs
Support
optoelectronic isolation