Set-Up; Guided Installation Via An Installation Wizard - IFM SU9020 Operating Instructions Manual

Ultrasonic flow meter
Table of Contents

Advertisement

SU2020 SU2021 SU2621 SU8020 SU8021 SU8621 SU9020 SU9021
9 Set-up
After power on and expiry of the power-on delay time, the unit is in the normal operating mode. It
carries out its measurement and evaluation functions and generates output signals according to the
set parameters.
During the power-on delay time the outputs are switched as programmed:
ON with normally open function (Hno / Fno)
OFF with normally closed function (Hnc / Fnc)
ON for detection of direction (dir.F)
OFF for frequency output (FRQ)
OFF for consumed quantity monitoring (ImP)
20 mA for analogue output (I)
9.1 Guided installation via an installation wizard
When changing from the process value display to the main menu via the [●] key for the first time, you
are asked whether you want a guided installation.
u Select [Yes] or [No].
w If [Yes] is selected, parameters, questions and instructions appear in succession. Use the [▲] and
[▼] keys to choose from the available options and the [●] key to confirm your selection.
w If [No] is selected, the main menu appears and the sensor functions according to the factory
settings. If necessary, change the factory settings. Ò See chapter Parameter setting.
The guided installation can be called up again at any time via the parameter [EF] > [CFG] >
[Guide].
During guided installation, the following setting options appear in succession:
1. [diS.R]: display rotation
2. [LanG]: display language
3. [Fdir]: flow direction
4. Output OUT1:
– [SEL1]: process value (flow or temperature) or diagnosis (flow direction or signal quality).
– [uni.T] / [uni.F]: standard unit of measurement
– [ou1]: switching signal (Hno, Hnc, Fno, Fnc), pulse signal/switching signal totaliser, frequency
signal
– configuration of the parameters according to the function selected for [ou1]:
limit values for switching signal: SP1, rP1, FH1, FL1
pulse value for totaliser: ImPS
switch point and reset for totaliser: ImPS1, rTo1
limit values for frequency signal: FSP1 (only for temperature), FEP1, FrP1
– [FOU1]: error behaviour of the output
5. Output OUT2:
– [SEL2]: process value (flow or temperature) or diagnosis (flow direction or signal quality).
– [uni.T] / [uni.F]: standard unit of measurement
– [ou2]: switching signal (Hno, Hnc, Fno, Fnc), pulse signal/switching signal totaliser, analogue
signal
22