Operating Instructions Safety System MGBS-P-L.-AP… Contents About this document ..................... 4 1.1. Scope ............................4 1.2. Target group ..........................4 1.3. Key to symbols ..........................4 1.4. Supplementary documents ......................4 Correct use ......................5 Description of the safety function ................6 Exclusion of liability and warranty ................. 7 General safety precautions ...................
Page 3
Operating Instructions Safety System MGBS-P-L.-AP… Mounting ......................18 10.1. Mounting examples ........................18 10.2. Actuating escape release ......................19 Electrical connection ..................20 11.1. Notes about .........................20 11.2. Safety in case of faults ........................21 11.3. Fuse protection for power supply ....................21 11.4. Requirements for connecting cables ....................21 11.5.
Important! Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box. (translation of the original operating instructions) 2527245-03-06/23...
Ì EN 60204-1 The safety system MGBS is only allowed to be operated in conjunction with the intended EUCHNER handle modules and the related connection components and accessories from EUCHNER. On the modification of system components, EUCHNER provides no warranty for function.
Operating Instructions Safety System MGBS-P-L.-AP… Table 1: Possible combinations for MGBS components Handle module Locking module MGBS-H… MGBS… Key to symbols Combination possible 3. Description of the safety function Devices from this series feature the following safety functions: Monitoring of guard locking and the position of the guard (interlocking device with guard locking according to EN ISO 14119) Ì...
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions.
Operating Instructions Safety System MGBS-P-L.-AP… 6. Function The device permits the locking of movable guards. The system consists of the following components as a minimum: coded handle module (transponder) and locking module. Whether the locking module learns the complete transponder code (unicode) or not (multicode) depends on the respective version.
Operating Instructions Safety System MGBS-P-L.-AP… Important! If the guard is open when the power supply is interrupted and is then closed, guard locking is activated. This can lead to persons being locked in unintentionally. The tongue on the handle module cannot be pulled out of the locking module and the guard is locked as long as the guard locking pin is extended.
Operating Instructions Safety System MGBS-P-L.-AP… 7. System overview 7.1. MGBS-P-… (optionally with escape release) Key: • Locking module or interlocking module • Optionally with escape release • Optionally with Extended version NOTICE Ì Depending on the version, additional controls and indicators may be integrated.
Operating Instructions Safety System MGBS-P-L.-AP… 8. Manual release Important! No further release functions can be retrofitted on Extended variants with control elements in position 1 (S1) and position 2 (S2). Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test should be performed after release.
Operating Instructions Safety System MGBS-P-L.-AP… 8.2. Emergency release This permits opening of a locked guard from outside the danger zone without tools. For mounting, see the mounting sup- plement. Important! Ì It must be possible to operate the emergency release manually from outside the protected area without tools.
8.3.2. Preparation for inner door handle AE-R-S1 NOTICE Various inner door handles with different axis lengths are available, as well as mounting plates and door handles/door knobs. You will find further information at www.euchner.com. Length required for actuation axis Profile width...
Operating Instructions Safety System MGBS-P-L.-AP… 8.4. Lockout mechanism The lockout mechanism can be secured with padlocks (see Fig. 1). This is intended to prevent people from being locked in unintentionally. The lockout mechanism does not fulfill any safety function. Key: •...
Operating Instructions Safety System MGBS-P-L.-AP… 9. Changing actuating direction of the locking module NOTICE Ì Please read the operating instructions of the device before use! Ì If a data sheet is included with the product, the information on the data sheet applies. Ì...
Operating Instructions Safety System MGBS-P-L.-AP… 10. Mounting CAUTION Locking modules must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective. Ì Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for bypassing an interlocking device. NOTICE Risk of damage to equipment and malfunctions as a result of incorrect installation.
Operating Instructions Safety System MGBS-P-L.-AP… 10.2. Actuating escape release • Press the red release knob to the end stop. Guard locking is released. ¨ • Actuate inner door handle 2527245-03-06/23 (translation of the original operating instructions)
Operating Instructions Safety System MGBS-P-L.-AP… 11. Electrical connection WARNING In the event of a fault, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated. Ì Monitoring outputs must not be used as safety outputs. Ì...
Use connection components and connecting cables from EUCHNER. Ì On the use of other connection components, the requirements in the following table apply. EUCHNER provides no warranty for safe function in case of failure to comply with these requirements. Observe the following requirements with respect to the connecting cables: For locking modules MGBS-…-AP-…-SAB-…...
Door position monitoring output X 2.3 Diagnostic monitoring output X 2.4 Solenoid operating voltage, 24 V DC X 2.5 n.c. 1) Only for standard EUCHNER connecting cable 11.6. Connector assignment of safety switch MGBS-…-AP-…-SH-… with plug connector M23 (RC18) Wiring diagram B Conductor color- Plug connector...
Safety output, channel B Diagnostic monitoring output Door position monitoring output 0VUB Electronics operating voltage, 0 V DC Solenoid operating voltage, 0 V DC 1) Only for standard EUCHNER connecting cable 11.8. Connector assignment of safety switch MGBS-…-AP-…-SII-… with plug connectors 2 x M12, 5-pin Wiring diagram D Conductor color-...
The user is responsible for safe integration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number of your switch in the search box. You will find all available connection examples for the device in Downloads.
A detailed example of connecting and setting the parameters of the control system is available for many devices at www.euchner.com, in the area Download / Applications / MGBS. The features of the respective device are dealt with there in greater detail.
Operating Instructions Safety System MGBS-P-L.-AP… 11.11. Connection of guard locking control 11.11.1. Guard locking control for variants with IMM connection Guard locking solenoid operating voltage, 24 V DC Guard locking solenoid operating voltage, 0 V DC Fig. 6: Connection example with IMM connection 11.11.2. Guard locking control for variants without IMM connection Guard locking solenoid operating voltage, 24 V DC Electronics operating voltage and guard locking...
Operating Instructions Safety System MGBS-P-L.-AP… 12. Setup 12.1. LED displays You will find a detailed description of the signal functions in chapter 13. System status table on page 29. Color STATE Green LOCK Yellow STATE LOCK 12.2. Teach-in function for handle module (only for unicode evaluation) The handle module must be assigned to the locking module using a teach-in function before the system forms a functional unit.
Operating Instructions Safety System MGBS-P-L.-AP… 12.2.1. Teaching-in handle module 1. Establish teach-in standby: - Devices in the condition as supplied: unlimited teach-in standby after switching on - Locking module already taught-in: teach-in standby is available for approx. 3 min. after switching on Teach-in standby indication, STATE LED flashes 3x repeatedly.
Operating Instructions Safety System MGBS-P-L.-AP… 13. System status table LED indicator Output Operating mode State closed Normal operation, door closed and locked 1 x Normal operation closed Normal operation, door closed and not locked verse open Normal operation, door open open Device in teach-in standby Teach-in operation closed...
Operating Instructions Safety System MGBS-P-L.-AP… 14. Technical data NOTICE If a data sheet is included with the product, the information on the data sheet applies. 14.1. Technical data for safety switch MGBS-AP Value Parameter Unit min. typ. max. General Material - Switch head Die-cast zinc - Switch housing...
Operating Instructions Safety System MGBS-P-L.-AP… Value Parameter Unit min. typ. max. Monitoring outputs OL, OI, OD p-switching, short circuit-proof Output voltage 0.8 x UB V DC Max. load Solenoid Solenoid operating voltage IMP (reverse polarity protected, DC 24 V +10%/-15% regulated, residual ripple < 5%) Solenoid current consumption I Connection rating Duty cycle...
MGBS-P-I1-AP SERIES MGBS-P-I2-AP SERIES MGBS-P-IBI-AP SERIES MGBS-P-L1-AP SERIES MGBS-P-L2-AP SERIES MGBS-P-LBI-AP SERIES Responsible Party – U.S. Contact Information EUCHNER USA Inc. 1860 Jarvis Avenue Elk Grove Village, Illinois 60007 +1 315 701-0315 info(at)euchner-usa.com http://www.euchner-usa.com (translation of the original operating instructions) 2527245-03-06/23...
Operating Instructions Safety System MGBS-P-L.-AP… 14.3. Dimension drawings of variants Plug connectors 2 x M12 Plug connector M23 Cable exit C Cable exit A Cable exit C Cable exit A 2527245-03-06/23 (translation of the original operating instructions)
Page 34
Operating Instructions Safety System MGBS-P-L.-AP… With auxiliary key release With release, automatic return max. 50 With emergency release With wire front release (bowden) 21,5 32,4 (translation of the original operating instructions) 2527245-03-06/23...
Internet: www.euchner.com 18. Declaration of conformity The EU declaration of conformity can be found at www.euchner.com. Enter the order number of your device in the search box. The document is available under Downloads. 2527245-03-06/23 (translation of the original operating instructions)