ABB GPS2436 User Manual page 76

Table of Contents

Advertisement

Output Current
1, 2
Float/Boost Voltage
Total Harmonic Distortion
Regulation
Ripple
Noise
Current Limit Set Point
Width
Height
Depth
Weight
Efficiency
Heat Release
NE100AC24ATEZ
52Vdc, 40A
52Vdc, 50A
54.5Vdc, 40A
54.5Vdc, 50A
55Vdc, 55A
NE100AC24ATEZTEZ
52Vdc, 100A
54.5Vdc, 80A
54.5Vdc, 100A
54.5Vdc, 110A
Storage Relative Humidity
Audible Noise
EMC
Safety Standard
Certification Marks
Page 76
© Copyright 2023 ABB. All rights reserved.
Output NE100AC24ATEZ (Continued)
6,000W maximum
110Adc maximum from -40°C to +45°C 85Adc at +60°C
60Adc at +70°C 47.5Adc at +75°C
Rectifier self-derates at approximately
1.5 amperes per degree C (+45°C to +60°C)
2.5 amperes per degree C (+60°C to +75°C)
42-58Vdc
<5% at Nominal Vac and >50Adc
±0.5%
100 mVrms
< 2mV psophometric
30A-110A
5.25 in. (133.35 mm)
8 in. (203.2 mm)
19.75 in. (501.65 mm)
20 lbs. (9 kg)
> 90% typical
Per rectifier:
231W [788.9 BTU/hr]
288W [983 BTU/hr]
242W [827 BTU/hr]
302W [1,030 BTU/hr]
332W [1,133 BTU/hr]
463W [1,578 BTU/hr]
52Vdc, 80A
577W [1,966 BTU/hr]
485W [1,654 BTU/hr]
605W [2,060 BTU/hr]
666W [2,266 BTU/hr]
5% to 90%
< 52dBA
EN 50022, level B, conducted and radiated (CISPR 22)
Standards Compliance
EN 60950 (IEC950)
UL, VDE, CE
Rectifiers are individually UL Recognized and/or CSA Certified to UL1950 and CSA
C22.2 No 234/950. Rectifiers are also approved to IEC-950/EN60950 by an EC
Notified
Body and have outputs classified as SELV.
Mechanical
Environmental