7.
Thermal Comp
Enabled
High Temp Comp
Volt Step Down
High Comp Limit
Decrease
Nominal Temp
Low Temp Comp
Low T Comp
Low Comp Limit
Increase
Page 61
© Copyright 2023 ABB. All rights reserved.
The configuration of this field selects the batter type, Flooded or
Valve Regulated (sealed). This parameter is used in reserve time
Type
prediction and enhanced battery test features. Move the cursor to
the field and use the <+> or <-> key to adjust the threshold value.
Press <ENTER> to save the change.
This feature allows dynamic control of sealed cell battery voltage as a
function of temperature.
Enables or Disables the Thermal Compensation Feature. Move the
cursor to the field and use the <+> or <-> key to Enable or Disable.
Press <ENTER> to save the change.
This feature allows the system to compensate for high temperatures.
Battery step temperature can be set from
temperature, the system voltage is reduced by 0.17 X # of cells/string.
This sets the maximum temperature for which thermal compensation
is active.
This sets the slope (mV/degC) for high temperature compensation.
This field set the temperature at which no compensation is
required. The system voltage is at the setpoint float mode.
This feature allows the system to compensate for low temperatures.
This enables or disables the low temperature compensation feature.
This sets the minimum temperature for which thermal compensation is
active.
This sets the slope (mV/degC) for low temperature compensation.
GPS2436_MAN
113-185F. At