Step
The Remote Peripheral Monitoring feature has been designed into the MCR1 board and requires no additional
NOTE:
circuit packs. Monitoring and control modules ARE required, based on the application.
This section only describes a single module connection to the controller. Modules MUST BE PROGRAMMED after
they have been installed or they may not function properly. Detailed connection and configuration information
NOTE:
may be found in the User's Guide for Millennium II Controller Advanced Features manual.
Using the RPM bus cable (Ordering Code 407377704), wrap the cable through the EMI inductor bead twice. Place
1.
the bead approximately 3 inches from the end of the cable.
Connect the bus cable to:
TB-1 Pin Assignments
2.
9 or 10
*connections of the bus wire are NOT polarity sensitive.
3.
Secure the module connection unit and route the wires through the open- faced bottom of the connection unit.
Make the connections to TB2 on the connection unit:
TB-2 Pin Assignments
4.
SHIELD
*connections of the bus wire are NOT polarity sensitive.
* there are 2 IN, and 2 OUT connections. Either one may be used.
5.
Locate the control unit. This is the half with circuitry on it.
In the lower right hand side of the control unit (inside), are two rotary switches. Set SW-1 (LO) to 1. The module
will be recognized as 01 by the controller. Other modules added cannot have the same address or 00 for the
6.
address.
7.
Carefully attach the control unit to the connection unit using the ribbon connector.
This connector/cable is not keyed, so be careful to line up the pins properly.
NOTE:
After approximately 1 minute, the green LED on the front of the module will blink once approximately every 5
8.
seconds. Detailed troubleshooting information may be found in the User's Guide for Millennium II Controller
Advanced Features manual.
Page 36
© Copyright 2023 ABB. All rights reserved.
TB-1 Pin Descriptions
6
8
FNGD
RPM Conductor Color
IN
Blue or White
OUT
Blue or White
Bare wire
Action
RPM Conductor Color
*6
Blue or White
*8
Blue or White
Bare wire
RPM Conductor Description
Power/Communications
Power/Communications
GPS2436_MAN
RPM Conductor Description
Power/Communications
Power/Communications
Shield