Rectifier

Rectifier Specifications850022020 GPS2436 Prod Man r01.docx
Voltage Range
Frequency Range
Power Factor
AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the rectifier internal surge
protection. Protection must be provided external to the GPS system, if necessary, to limit surge energy reaching the rectifiers.
Site surge protection must be coordinated with rectifier internal surge protection and must clamp at a lower voltage than the
rectifier internal protection. The internal protection voltage and current characteristics of the rectifiers are as follows:
Phase to Phase Voltage
320Vac (RMS)
620V maximum clamping
810Vpeak
High Voltage Shutdown
Internal Selective High Voltage Shutdown
(ISHVSD)
Backup High Voltage Shutdown (BUHVSD)
1
Output Power
1
Output Current
Float/Boost Voltage
Total Harmonic Distortion
Regulation
Ripple
Noise
Current Limit Set Point
1. Selectable/programmable through Galaxy Controller
2. Factory default settings – actual range is 44 - 60Vdc
3. Factory default settings – Float/Boost range is 58.51 - 60.53Vdc, Equalize range is 65.2 - 67.0Vdc
Page 75
© Copyright 2023 ABB. All rights reserved.
Electrical
Input
175-275Vac, 2-wire, single phase
(150 Vac - 300 Vac with reduced performance)
45 - 66 Hz
> 0.98 at > 50% rated output
MOV Conduction Current
0A
1mA (DC test current)
100A peak (8 x 20's)
Output All
Float:
56.0Vdc Nom.
Boost: 56.0Vdc Nom.
Equalize: 59.52 ± 1Vdc Nom.
Float/Boost: 59.52Vdc
3
Equalize:
66.0Vdc
Output NE100AC24ATEZ
3,000W maximum
55Adc maximum from -40°C to +65°C 42.5Adc at +75°C
30Adc at +85°C
Rectifier derates at approximately
1 ampere per degree C (+65°C to +85°C)
21-29Vdc
<5% at full load
±0.5%
100 mVrms
< 2mV psophometric
15A-55A
GPS2436_MAN
1, 2
1, 2
1, 2
3
Rev. 1.3