6.15
Burner flame goes out during operation
If the flame accidentally goes out during operation, the control
box carries out a recycle (i.e. it repeats the start-up phase once,
and makes a further ignition attempt).
6.16
Stopping of the burner
The burner can be stopped by:
intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
position selector "OFF/ON" (Fig. 5 on page 12) to "OFF" (0);
6.17
Measuring the flame signal
The burner is fitted with a sensor to check that a flame is present.
The minimum current for control box operation is 70 µA. The op-
erator Panel displays "30%" (see List of parameters, parameter
954).
The burner provides a much higher current, so controls are not
normally required.
If, however, you want to measure the current of the flame sensor,
follow the instructions as described in "Maintenance pro-
gramme" on page 54.
6.18
Final checks (with burner operating)
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
Turn the air pressure switch to the maximum end of scale
position
Turn the oil maximum pressure switch knob to the mini-
mum end of scale position
Turn off the burner and cut off the power
Disconnect the minimum gas pressure switch connector
Turn the oil minimum pressure switch knob to the maxi-
mum end of scale position
Obscure the flame sensor
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
WARNING
Start-up, calibration and operation of the burner
If the flame is still absent, the control box goes into lockout.
removing the transparent protection that covers the Operator
Panel (after loosening the relative screw), and intervening
on the Panel itself as explained in the "Manual lockout pro-
cedure.
S8171
The burner must stop
The burner must stop in lockout
The burner must not start
the burner must stop in lockout due to flame loss
53
GB
P
V
h min s
%
Fig. 51
Tab. U
20121288