6.11

Backup / Restore procedure

At the end of the Start-up procedure it is wise to carry out a
backup, creating a copy of the data memorised on the LMV 26...,
in the RDI 21 display panel.
This will allow the data to be used for programming a new LMV
26... or to return to the memorised settings of the same LMV 26...
We suggest that this operation be carried out at
the end of any intervention that involves modifica-
tions to what has been set on the cam.
WARNING
WARNING
This will allow you to carry out a restore in a simple
manner on a new cam supplied as a replacement
part, without having to reprogramme the system.

6.11.1 Backup

To perform the backup, proceed as follows:
 access the Parameters Level referring to Access procedure
with password.
The display screen displays the parameters group 400.
P
With the key "-":
Select the parameters group 000:
P
The 000 parameter blinks, confirm using the "i/reset" key:
The display screen shows parameter 050 blinking:
P
confirm with the key "i/reset":
Start-up, calibration and operation of the burner
V
h
min
s
%
h min s
%
/reset
h min s
%
/reset
The parameter bAC_UP appears on the display screen:
P
confirm with the key "i/reset":
The display screen shows the following value:
P
Use the button "+":
The value will be set to 1. Value 1 is flashing:
P
confirm with the button "i/reset" to activate the backup process.
The value 1 appears on the display screen:
P
After approx 5 seconds (it depends on the duration of the pro-
gramme), the 0 value appears on the display screen, this is to in-
dicate that the backup process has been completed correctly.
P
45
GB
V
h min s
%
/reset
V
h min s
%
h min s
V
/reset
V
h min s
%
V
h min s
%
20121288