Riello RLS 68/E MX Installation, Use And Maintenance Instructions page 50

Dual fuel light oil / gas burners
Table of Contents

Advertisement

Parameter
No.
Description
Standby time before a new attempt in event of com-
munication fault
142
Set values:
0 = not active
1 = .... 7200 s
143
Reserved
144
Reserved
Peripheral address for Modbus
145
Set values:
1 ... 247
Baud Rate for Modbus
Set values:
146
0 = 9600
1 = 19200
Parity for Modbus
0 = none
147
1 = odd
2 = even
Selection of the burner operation during the interrup-
tion of the switch-over with the system of remote man-
agement.
Set values:
With modulating operation the settings of the values
are the following:
148
0...19.9 = burner switched off
20...100 = 20...100% modulation field of the burner.
With stage operation:
0 = burner off P1, P2, P3
No setting = no function in the event of communication
interruption
161
Total number of errors
162
Hours of operation (that can be reset)
163
Total hours of power supply to control box
164
Total number of start-ups (that can be reset)
166
Total number of start-ups
Volumetric delivery of fuel in the selected unit of meas-
167
urement (that can be reset)
200
BURNER CHECKS (fuel 0)
Burner operation mode (fuel supply line, modulating/
stage, servomotors, etc.)
-- = not defined (eliminate curves)
1 = Gmod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2 stage
6 = Lo 3 stage
7 = Gmod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
201
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
Stopping of the program
0 = deactivated
1 = pre-purging (Ph24)
208
2 = Ignition (Ph36)
3 = Interval 1 (Ph44)
4 = Interval 2 (Ph52)
Alarm as the pre-purging phase begins;
210
0 = Deactivated;
1 = Activated
20121288
Start-up, calibration and operation of the burner
No. of
measure-
elements
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Unit of
Values interval
Modifica-
tion
Min.
ment
s
Modification
0s
-
Modification
1
s
Modification
10s
-
Modification
1
-
Modification
0
-
Modification
0
Modification /
%
0%
zero setting
-
Reading only
0
h
Reset
0 h
h
Reading only
0h
-
Reset
0
-
Reading only
0
3
m
, l,
Reset
0
3
ft
, gal
Modify/set to
-
1
zero
-
Modification
0
-
Modification
0
48
GB
Degree of
Predefined
precision
setting
Max.
7200s
1s
120s
8
1
1
60s
1s
30s
247
1
1
1
1
1
2
1
0
100%
0.1%
Not defined
65535
1
0
999999h
1 h
0h
999999h
1h
0h
999999
1
0
999999
1
0
99999999
1
0
22
1
Not defined
4
1
0
1
1
0
Access mode
Service Mode
Info Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Info mode
Info mode
Info mode
Info mode
Info mode
Info mode
Service Mode
Service Mode
Service Mode