Two control variants can be implemented
with the ER 60 GVZC EC control:
● Permanent base load with connectible
rated load (standard circuit).
● Connectible base and rated load
(circuit variant).
The jumper [S] can be used to set the start
delay time (0, ½, 1, 2 or 3 minutes) and
overrun time (0, 1, 3, 6 or 15 minutes).
Jumper settings on plug connector [15.2]
Factory
setting
Start delay
0 minutes
½ minute
1 minute
2 minutes
3 minutes
Overrun time
0 minutes
1 minute
3 minutes
6 minutes
15 minutes
NOTICE
Damage to GVZC EC board if jumper is
changed using inappropriate tool.
 Only remove jumper with appropriate
tool.
To adjust the start delay and overrun time,
plug the two jumpers [S] in the desired
position.
14. Installation of fan insert and cover

14.2 Installing fan insert/exhaust air

element  Fig. 16
The ER fan insert / The Centro exhaust air
element is inserted in recess-mounted
housings ER-UP/G, ER-UPD or ER/UPB
as follows.
1. Switch off mains fuse, secure and fit
warning sign.
2. Remove plaster protective cover [41]
and clean any dirt off the recess-mounted
housing.
3. Ensure that the fan type ticked in the
housing box matches the type to be fitted.
4. Check ease of movement of shut-off
shutter/backflow preventer.
When installed, the shut-off shutter/back-
flow preventer must close automatically.
With ER-UPD and ER-UPB, this must
close automatically when the yoke spring
used is pressed (exception - upwards air
outlet,  chap. 11.5.2).
With ER-UPD and ER-UPB ensure that
the soldered strut is inserted correctly
 chapter 11.5.2.
5. Check that the housing floor seal is
correctly positioned and insert properly.
NOTICE
The noise level will increase if the
housing floor seal [13] is fitted
incorrectly. Degree of protection not
guaranteed if housing floor seal [13]
is positioned incorrectly.
 The housing floor seal must lie flat and
without any creases in the housing.
35