2.2.1.2
Technical data
Technical data
Task within the EtherCAT system
Transmission medium
Cable length between two stations
Protocol
Data transfer rates
Configuration
Bus interface
Delay
Power supply
E-Bus current consumption
E-bus power supply (5 V)
(at higher current consumption the EL9410
power feed terminal can be used in addition)
General data
Dimensions (W x H x D)
Weight
Permissible ambient temperature range during
operation
Permissible ambient temperature range during
storage
Permissible relative humidity
Mounting [} 58]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approvals / markings
Ex markings
Standard
Marking
ATEX
II 3 G Ex nA IIC T4 Gc
IECEx
Ex nA IIC T4 Gc
cFMus
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc
*) Real applicable approvals/markings see type plate on the side (product marking).
EK112x, EK15xx
EK1122-0008
Coupling of EtherCAT junctions via M8
Ethernet/EtherCAT-cable (min. CAT 5), shielded
100 m (100BASE-TX)
EtherCAT
100 Mbit/s
not required
2 x M8
approx. 1 µs
from E-bus
typ. 220 mA
max. 2000 mA (-25°C ... +55°C)
max. 1000 mA (> +55°C)
EK1122-0008
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
approx. 65 g
-25°C ... +60°C
(extended temperature range)
-40°C ... + 85°C
95%, no condensation
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 63], ATEX [} 59], IECEx [} 60], cFMus
[} 62]
Version: 3.6
Product overview