Beckhoff EtherCAT EK112 Series Manual page 18

Table of Contents

Advertisement

Product overview
2.1.1.2
Technical data
Technical data
Task within the EtherCAT system
Transmission medium
Cable length between two Bus
Couplers
Protocol
Data transfer rates
Bus connection
Delay
Configuration
General data
Power supply
Current consumption
Dimensions (W x H x D)
Weight
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative humidity
Mounting [} 58]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approvals/markings
Ex markings
Standard
ATEX
IECEx
cFMus
*) Real applicable approvals/markings see type plate on the side (product marking).
18
EK1122
Coupling of EtherCAT junctions
Ethernet/EtherCAT cable (min. CAT5), shielded
max. 100 m (100BASE-TX)
EtherCAT
100 Mbit/s
2 x RJ45
typ. 1 µs
no address and configuration settings required
EK1122
from E-bus
typ. 220 mA
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
approx. 70 g
-25°C ... +60°C
(extended temperature range)
-40°C ... + 85°C
95%, no condensation
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 63], ATEX [} 59],
IECEx [} 60], cFMus [} 62]
EK1122
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T135 °C Dc
Ex nA IIC T4 Gc
Ex tc IIIC T135 °C Dc
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc
Version: 3.6
EK1122-0080
Coupling of EtherCAT junctions,
Fast-Hot-Connect technology
[} 19]
EK1122-0080
CE, cULus [} 63], ATEX [} 59]
EK1122-0080
II 3 G Ex nA IIC T4 Gc
-
-
EK112x, EK15xx

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ethercat ek15 series

Table of Contents